Villa electrics: sockets, circuits and the DB, room by room
A socket every 4 m, 30–45 cm off the floor, 60 cm to 2 m from water, one circuit per AC: the Saudi and Dubai electrical rules to check on your villa plans.
In a Saudi villa, the residential code wants a socket at least every 4 m along the walls, 30 cm or more above the floor and 60 cm from any tap or basin. In Dubai, DEWA allows five sockets on a 20 A radial circuit, puts sockets at 45 cm and keeps them 2 m from water. Both markets use the same British-style 13 A three-pin socket with 30 mA RCD protection. Fix these numbers with your engineer before the walls are closed: moving a socket after plastering means cutting tiles and paint.
Villa electrics at a glance
Item
Saudi Arabia (SBC 1101-1102)
Dubai (DEWA)
Supply
230/400 V, 60 Hz
230/400 V, 50 Hz
Socket type
13 A, BS 1363 style (type G)
13 A, BS 1363, switched and shuttered
Distance between sockets
4 m maximum along the wall
–
Socket height
30 cm minimum (rooms and majlis)
45 cm
Kitchen sockets
30 cm above the worktop
25 cm above the worktop
Distance from water
60 cm minimum
2 m minimum; no sockets in bathrooms
Outdoor sockets
1 m above the ground
IP65 weatherproof
Earth-leakage protection
RCD on socket circuits
30 mA RCD on sockets up to 20 A
Sockets per circuit
Set in the load schedule
5 on a 20 A radial; 10 on a 30 A ring (not kitchens)
Lighting circuit
Set in the load schedule
2,000 W and a 16 A breaker maximum
Air conditioning
Own circuit recommended
Own circuit per unit, 20 A and 4 mm² minimum
Distribution board
Load schedule per floor
One per floor; top at 2 m maximum
1. How many sockets per room
The codes set spacing, not a number per room. A good minimum comes from the UK house-builders' standard (NHBC), which counts single outlets, so a double socket counts as 2:
Room
Minimum outlets
Gulf tip
Kitchen
8
At least 3 free above the worktop
Living room or majlis
8
2 near the TV; 1 by each seating wall for chargers
Main bedroom
6
A double socket on each side of the bed
Other bedrooms
4
Plus 1 at the desk
Dining room
4
1 near the buffet for the coffee and tea flasks
Hall or landing
2
For cleaning
Then check the Saudi 4 m rule on your plans: no stretch of wall longer than 4 m without a socket.
2. Heights and positions
Sockets: at least 30 cm above the finished floor in Saudi Arabia; 45 cm in Dubai.
Kitchen:30 cm above the worktop in Saudi Arabia, 25 cm in Dubai.
Switches:125 cm above the floor in Dubai.
Mark the TV wall, the bed, the desk and the majlis seating on the plan before the electrician chases the walls.
3. Kitchen, laundry and water heaters: their own circuits
In Dubai, the cooker, each water heater, the washing machine and the sauna each need a separate circuit from the distribution board (DB). The cooker switch sits within 2 m of the cooker, and the water heater switch goes outside the bathroom, on a 30 mA RCD. Ask for the same in Saudi Arabia: the sample load schedule in the Saudi code checklist puts the water heater on its own line, with its own breaker and cable. See the water heater guide to size the heaters first.
4. Bathrooms and wet areas
Dubai: no sockets and no switches inside bathrooms; sockets and switches at least 2 m from any tap, basin or sink.
Saudi Arabia: sockets at least 60 cm from any water source, on RCD protection.
Keep the light and fan switches outside the door; in Dubai, shaver sockets also go outside the bathroom.
5. Air conditioning: one circuit per unit
DEWA gives each room AC unit its own circuit, with a breaker of at least 20 A and 4 mm² cable. Split units need a double-pole isolating switch next to the unit. Size the units with the BTU calculator, then count one circuit for each. Our guide to AC types explains split, ducted and package units.
6. The distribution board (DB)
One DB per floor, feeding only that floor; in Saudi Arabia the plans must show a load schedule for each DB per floor (cable size, breaker, conduit).
Not in a bedroom, bathroom, kitchen, store, or under the stairs; top of the board at 2 m maximum.
Every breaker labelled with the circuit it feeds.
7. Outside, roof and garden
Outdoor sockets sit at least 1 m above the ground in Saudi Arabia. In Dubai, all outdoor boxes and fittings must be IP65 weatherproof, with conduits sealed at both ends. Plan sockets at the outdoor majlis, the barbecue, the roof (for maintenance) and the gate.
Example: plan the majlis and count the lighting circuits
A majlis of 5 × 7 m: the perimeter is 2 × (5 + 7) = 24 m. With a socket at least every 4 m: 24 ÷ 4 = 6 socket positions. Six double sockets give 6 × 2 = 12 outlets, above the minimum of 8.
Lighting on the ground floor, Dubai rules: DEWA counts 100 W per lighting point when the fittings are not chosen yet, and 2,000 W maximum per circuit, so 2,000 ÷ 100 = 20 points per circuit. A ground floor with 45 points needs 45 ÷ 20 = 2.25, so 3 lighting circuits.
Before you call an electrician
Mark the furniture on the plans: beds, TV, desk, majlis seating, kitchen appliances.
Check the numbers above: spacing, heights, distance from water, outlets per room.
Ask for the load schedule of each DB: one circuit per AC unit, water heater, cooker and washing machine.